Does HART Require Additional Wiring?

06/09/2026

Answer

Normally, no.
In a point-to-point installation, HART communication uses the same pair of wires as the standard 4–20 mA signal, so separate communication wiring is generally not required. However, the loop must have sufficient impedance for reliable HART communication. If the existing loop resistance is too low, additional resistance may be required.