Answer
A common cause is insufficient loop resistance or an incompatible device in the communication loop.
Check whether the total loop impedance meets the HART communication requirements and whether the DCS I/O card already provides the necessary resistance. Also verify the wiring, power supply, and communicator connection.
For intrinsically safe installations, confirm that the safety barrier or signal isolator is HART compatible, as an incompatible barrier or isolator may prevent HART communication.